JANUARY 2002
Planning and Designing With a grasp of gas sensor basics, and a methodical plan for installing the detectors, you can build a system smart enough to save your life.
Wolfgang Jessel, Dräger Safety AG & Co. KGaA Whenever combustible and/or toxic substances are stored, processed, or transported in the chemical industry, the potential risks are high. For example, if pressurized gases are accidentally released, pipelines leak, or combustible liquid vapors escape through damaged valves or leaking seals, the result can be a hazardous condition. In the case of:
First, Some Questions
Answering the first group of questions will give a general outline of the task at hand, clarifying the operational conditions and the intended purpose, i.e., whether toxic gases (or gases that can have a suffocating effect) need to be detected to protect workers or whether combustible gases (or vapors) need to be detected to help prevent explosions.
Gas Sensors Electrochemical. Under certain conditions, an electrochemical sensor (see Photo 1) can oxidize or reduce reactive gases or vapors diffusing through a hydrophobic membrane, thus coming into contact with an electrode embedded in a special electrolyte (see Figure 1).
The catalytically activated electrode reaction then produces ions and electrons, the latter forming a current in the outer electrical circuit connected to the sensor’s electrodes. With a third electrode integrated in a potentiostatic electronic circuit, the sensor voltage is kept constant, with the result that the current is proportional to the gas concentration. To optimize temperature compensation there is a negative temperature coefficient resistor placed in the interior of the sensor. Infrared. The IR measuring principle (see Figure 2 and Photo 2) is based on the fact that gas molecules are excited by IR light of a certain wavelength and so produce vibrations while partly absorbing energy from the light.
Compared to the original IR light intensity, the attenuated intensity within a defined fixed optical path is a measure for the gas concentration. A second beam with a wavelength not absorbed by gas can be used to measure the original IR light intensity. This is used to make the IR system tolerant to dust and alterations to the intensity of the light source itself. Catalytic. The catalytic measuring principle (see Photo 3 and Figure 3) is highly suitable for the detection of combustible gases and vapors.
Two ceramic beads (pellistors) with embedded platinum coils are heated to ~450°C. One pellistor is activated by a catalytic material that, at the given temperature, oxidizes the gas and thus forms additional heat which can be detected by measuring the resistance of the platinum coil. Using a Wheatstone bridge with a second, deactivated pellistor as a reference, the bridge current is approximately proportional to the gas concentration in the 0%–100% range of the lower explosive limit (LEL). As each of these measurement technologies can have advantages and disadvantages depending on its intended application, the most reliable information about the suitability of a particular method to the task in hand is likely to be available from manufacturers, supported by their application laboratories. Spot, Area, and Fence Monitoring. A distinction is made among three basic sensor positioning strategies, though naturally it may be necessary to combine or adapt the strategies to suit a particular application.
Spot monitoring can be accomplished by the highly targeted use of just a few gas sensors; area monitoring requires a large number. The latter method is used, for example, to monitor combustible liquids in storage, where the sensors are distributed in a grid-like manner across the entire area. In this type of application, a sensor can monitor an area of 500–1000 ft2, while in solvent storage areas a reasonable compromise appears to be a circular area with a diameter of ~30 ft (total surface area ~800 ft2). When planning installations, however, area monitoring is often favored simply because at the time of planning the potential sources of leakage are as yet unknown. This is bound to be a costly and indeed the most maintenance-intensive solution which, in many cases, later proves to have been unnecessary. The more precisely the locations of potential gas leaks can be pinpointed, the more economically planners will be able to design the gas detection installation. From a safety point of view, fence monitoringûas a method of gas detection is little more than informative, since targeted countermeasures are virtually impossible by the time an alarm is given. Countermeasures, after all, can be effectively implemented only if there is adequate information available concerning the time and the location of the leakage. While area monitoring provides far less precise information than spot monitoring, fence monitoring does not give any specific information at all about the location and time of the gas leak. This is particularly true when open-path systems, e.g., photoelectric barriers that detect the potential danger caused by a gas, are used for fence monitoring. Certain basic rules must be followed in positioning a sensor:
If for whatever reason a sensor cannot be positioned in the immediate vicinity of the potential leakage source, it is possible to sample air continuously and thus lead the gas sample past the sensor. This method is expensive, however, not only because the airflow must be monitored, but also because any adsorption in the pipeline or condensation due to a temperature gradient must be taken into account. If worse comes to worst, the gas must be completely conditioned, possibly even to the extent of ensuring explosion protection. Air sampling, of course, also increases the reaction time of the gas detection system. Calibration. As is true of virtually every measuring device, gas detection instruments perform a relative measurement, i.e., they measure a gas concentration and compare it to a known concentration that is not actually present but which was communicated to the device during its last calibration. The quality of measurement will therefore always depend to a significant extent on how the last calibration was performed and—if the measurement quality is subject to aging (e.g., through long-term zero point drifts and sensitivity)—when calibration was performed. A fundamental prerequisite for reliable measurements is an accurately performed calibration. However precise the device may be, poor calibration practices can cause it to produce readings that are completely false. Especially when calibrating with test gases with a very low concentration of the target gas (effects of absorption), specialized knowledge is needed and in many cases calibration cannot be performed on the spot. (There is help in the form of precalibrated, plug-and-play electrochemical sensors.) Catalytic sensors should be calibrated with the gas to be detected. If the substances in question are combustible liquids, it is possible to generate concentrations of, for example, 50% LEL cyclohexane in a calibration chamber directly on site. Although calibration with the target gas gives the best calibration results, the use of previously determined calibration factors has also become an established method. With catalytic sensors, however, this method has a greater potential for error because these calibration factors are subject to greater fluctuations and aging. IR sensors do not have this disadvantage. The best general rule is to calibrate a sensor under real-life conditions.
Gas Detection Systems This knowledge is essential, as it proves that the safety of an installation cannot be increased by lowering the alarm thresholds below a certain limit. In safety technology, incorrect alarms are regarded as extremely dangerous; if they occur too often they will be ignored, possibly leading to serious trouble in the event of a genuine alarm. The correct lower alarm limit can be calculated only on the basis of the sensor data and the actual operating conditions. The lowest limit should be no less than six times the zero-point standard deviation under actual operating conditions. Depending on the target gas, the type of sensor, and the application, the lowest reasonable alarm threshold may be predetermined by the gas concentrations present or by the properties of the detection instruments or sensors. When lower alarm limits are desirable for occupational health or safety reasons, they can be achieved only with considerable effort and/or equipment. In such cases, a compromise acceptable to everyone concerned must be worked out in the planning phase. Alarm Messages. Two alarms have been demonstrated sufficient in gas detection systems. The pre-alarm provokes a reaction, either a prearranged set of responsive actions or the issuance of instructions appropriate to the particular event. Should the alarm condition persist, the main alarm is triggered and more aggressive actions are taken, such as switching off machinery and clearing the area. Ideally, the main alarm will rarely—preferably never—be necessary.
Adapted from “Planning and Designing Gas Detection Systems” by Dr. Wolfgang Jessel, appearing in Dräger Review 85, April 2000, by permission. Dr. Wolfgang Jessel is an Applications Engineer and Physicist, Dräger Safety AG & Co. KGaA, Revalstrasse 1, D-23560 Leubeck, Germany; 49-451-8820, fax 49-451-882-2080, wolfgang.jessel@draeger.com. For more information, contact Draeger Safety, Inc., Gas Detection Systems Division, 10450 Stancliff, Ste. 220, Houston, TX 77099; 281-498-1082, fax 281-498-5190.