Figure 6. In a two-wire 4­20 mA circuit configuration, a 4 mA current is used to power a transducer, and an incremental 0-16 mA current transmitted over the same pair of wires is proportional to the measured pressure. Current output permits transmission over a long distance without loss of accuracy due to the cable resistance. The external transistor forms the controllable current loop. The MCA7707 controls the voltage across resistor RA, and if a 50 value is selected, a 0.2­1.0 V range would have to be set during a calibration procedure. If necessary, the programmable gain amplifier output can be divided using resistors RB and RC.